Products

ACDB Panel

Final AC distribution point with integrated protection for localized facility safety and control.

V-SERIES AC

ACDB Panel

The final AC distribution point between inverter and grid, with integrated protection.

Our AC Distribution Boards are built to receive inverter output and pass it safely to the grid or plant distribution network. Enclosures are fabricated from 1.5 or 2.0 mm CRCA sheet with modular or draw-out construction, and are offered at IP45 for indoor installation or IP65 where the board sits outdoors alongside the inverter bank.

An ACDB sits immediately after the inverter in a solar installation and forms the last protected point before the supply joins the facility network or the utility grid. It operates at 415 V AC three phase, with ACB or MCCB incomers, AC surge protection and overload protection built in. Separate compartments are provided for the incomer, outgoing feeders, busbar and metering, and digital panel meters with indication lamps allow generation to be monitored at the point of connection.

Specifications

Technical Data

Detailed engineering breakdown of the ACDB Panel performance and build characteristics.

Structure IP 45 / IP 65 Indoor & Outdoor Type
Thickness 1.5 / 2.0 mm CRCA Sheet
Cable Entry Top / Bottom Side
Design Welded / Modular / Draw-out
Feeder & Compartment Incomer Feeder, Outgoing Feeder, Busbar Compartment, Cable Alley, Metering Compartment
Incomer MCCB / ACB
Metering Digital Panel Meters + Indication Lamp
Protection AC SPD + Overload Protection
Operating Voltage 415 V AC, 3 Phase
Outgoing MCCB / MCB / Changeover
Panel Wire 0.75 Sq.mm to 25 Sq.mm Single Core Copper Flexible Wire (FR/FRLS)
Busbar EC Grade Copper / Aluminium Flat Bar
De-rating Factor of Busbar Copper 1 Sq.mm = 1.6A | Aluminium 1 Sq.mm = 0.8A
Panel Accessories & Hardware SS 304 Nut Bolts, PU Gasket, Door Hinges, Lifting Hook
Paint Powder Coating with 7-Tank Pre-Coating Process
Ref. Standard IEC 61439
FAQ

Frequently asked questions

Straight answers to common questions about the ACDB Panel.

What does an ACDB do in a solar plant?

An ACDB sits immediately after the inverter. It receives the inverter output and passes it safely to the grid or plant distribution network, with protection, isolation and surge protection built in.

Why does an ACDB need different protection from an ordinary AC board?

Because it is fed by a current limited source. A grid tied inverter typically delivers between 1.1 and 1.5 times its rated output as fault current, for a few cycles, so a breaker chosen only against the grid fault current may never trip on the inverter side.

Which IP rating should an ACDB have?

We offer IP45 for indoor installation and IP65 where the board sits outdoors alongside the inverter bank. A sealed outdoor board holds heat, so the thermal design should be checked against the site ambient.

What protection is built into the ACDB?

The specification lists AC surge protection and overload protection, with MCCB or ACB incomers, MCCB, MCB or changeover outgoing devices, digital panel meters and indication lamps, at 415 V AC three phase.

Can one ACDB serve several inverters?

Yes, but the board should isolate each inverter individually so one can be worked on while the rest keep exporting.

What should I tell you before ordering an ACDB?

Send the inverter datasheet figures for rated output and maximum output fault current with its duration, the number of inverters, the grid side fault level and the interface protection your DISCOM requires, which differs between states.

Get In Touch

Inquiry Form

Fill out the form below for a technical consultation regarding our ACDB Panel.

This field is for validation purposes and should be left unchanged.

Ready to Power Your Industrial Future?

Consult with our engineering experts today for a customized power distribution strategy and optimized facility efficiency.

Request a Technical Audit